Rated power range: 16,000–63,000 kVA
HV winding rated voltage: 158 kV
LV winding rated voltage: 6.3 kV
Climatic category: U1 / UHL1
Т – Three-phase transformer.
R – Split LV winding.
D –
Natural oil circulation and forced air circulation.
N –
On-load tap changer (OLTC).
Х – Rated power, kVA.
150 –
HV voltage class, kV.
U1 or UHL1 –
Climatic category and installation type in accordance with GOST 15150
|
Technical characteristicsfor TRDN transformer, rated 32,000 kVA, standard losses
|
||||||
|
Rated power, kVA
|
Rated voltage, kV
|
Winding connection diagram and vector group |
Losses, W |
Short-circuit voltage, %
|
No-load current, %
|
|
|
No-load
|
Short-circuit
|
|||||
|
16000
|
158
|
Yn/D-D-11-11
|
16000
|
88000
|
20,0
|
0,8
|
| 32000 | 158 | Yn/D-D-11-11 | 159900 | 171900 |
20,5
| 0,7 |
| 63000 | 158 | Yn/D-D-11-11 | 43000 | 235000 | 17,8 | 0,55 |
| Transformer overall dimensions |
|||||||
|
Rated power, kVA
|
Length, (L) mm
|
Width, (B) mm
|
Height, (H) mm
|
Distance between channel centerlines
|
Oil weight, kg
|
Total weight, kg
|
|
|
Transverse axis (A), mm
|
Longitudinal axis (A1), mm
|
||||||
| 16000 | 5800 | 4220 | 5300 | 2000 | 1524 | 11200 | 42400 |
|
32000
|
6310
|
4450
|
6000
|
2000
|
1524
|
15090
|
58500
|
| 63000 | 6900 | 4850 | 6250 | 2500 | 1524 | 21750 | 95325 |