TDNP-4000–10000/35-U1(UHL1) type transformers for mobile substations

product
Power transformer, three-phase, two-winding, with forced air and natural oil circulation, rated power 4,000–10,000 kVA. Designed for installation in mobile transformer substations on truck semi-trailers. Designed and manufactured in accordance with GOST R 52719.
Get the cost
Application sent

By clicking the “Calculate” button, you consent to the processing of personal data.

Description

Power transformer, three-phase, two-winding, with forced air and natural oil circulation, rated power 4,000–10,000 kVA. Designed for installation in mobile transformer substations on truck semi-trailers. Designed and manufactured in accordance with GOST R 52719.

Power range

HV winding rated voltage: 35 kV
LV winding rated voltage: 10(6) kV

Transformer symbols

Т – Three-phase transformer
– Natural oil circulation and forced air circulation
– On-load tap changer (OLTC)
– Mobile
Х – Rated power, kVA
35 – Voltage class, kV
U1/UHL1 – Climatic version and placement category in accordance with  GOST 15150

Characteristic

Main Technical Characteristics
Parameter name Value
Transformer type TDNP-4000/35 TDNP-6300/35 TDNP-10000/35
No-load losses, kW 5,6 (4) 8 (5,5) 12 (7,6)
Short-circuit losses, kW 33,5 (31) 46,5 (40) 60 (55)
No-load current, % 0,7 0,7 0,65
Short-circuit voltage (HV–LV), % 7,5 7,5 10
Overall dimensions, mm
L — length 3800 3950 4600
B — width 2400 2450 2600
H — height 2750 2950 3050
Oil weight, kg 2500 3500 5700
Shipping weight, kg 9500 12000 19500
Total weight, kg 12000 14500 23500

Dimensional drawings

print
Power transformer, three-phase, two-winding, with forced air and natural oil circulation, rated power 4,000–10,000 kVA. Designed for installation in mobile transformer substations on truck semi-trailers. Designed and manufactured in accordance with GOST R 52719.
Get the cost
Please fill in all fields with *
Application sent

By clicking the “Calculate” button, you consent to the processing of personal data.

team
Tusov Artem Aleksandrovich
Deputy Director for Marketing and Sales

Can't decide?

Consultation and equipment selection over the phone

Your name

Phone

Your application has been submitted for development
[10]
By clicking the “Request a call” button, you consent to the processing of personal data.