TMNP-2500–6300-U1 (UHL1) type two-winding power transformers, skid-mounted

product
Power transformer, three-phase, two-winding, with natural oil circulation, equipped with on-load tap changer (OLTC). Automatic control is provided by a controller supplied together with the transformer. Designed for use in electric power transmission systems, ensuring minimized transmission losses in power lines. Skid-mounted (mobile) design. TMNP-type transformers ensure reliable power supply throughout their service life.
Get the cost
Application sent

By clicking the “Calculate” button, you consent to the processing of personal data.

Description

Power transformer, three-phase, two-winding, with natural oil circulation, equipped with on-load tap changer (OLTC). Automatic control is provided by a controller supplied together with the transformer. Designed for use in electric power transmission systems, ensuring minimized transmission losses in power lines. Skid-mounted (mobile) design. TMNP-type transformers ensure reliable power supply throughout their service life.

Power range

Rated power range: 2500–6300 kVA
HV winding rated voltage: 35 kV
Climatic category: U1 or UHL1

Transformer symbols

Т – Three-phase transformer
М – Oil-immersed cooling with natural oil and air circulation
– On-load tap changer (OLTC)
– Skid-mounted (mobile) design
Х – Rated power, kVA.
35 – Voltage class HV, kV.
U1 or UHL1 – Climatic category and installation type in accordance with GOST 15150

Characteristic

Main technical characteristics for TMNP-2500–6300/35-U1 (UHL1) type transformers
Transformer type
Rated power, kVA
Rated voltage, kV
Winding connection diagramand vector group
Losses, kW
Short-circuit voltage, %
No-load current, %
HV LV No-load
Short-circuit
TMNP-2500/35
2500
35
11; 6,3
Yn/D-11
4,1 23,5
6,5
0,8
TMNP-4000/35
4000
35
11; 6,3
Yn/D-11
5,6
33,5
6,5
0,5
TMNP-6300/35
6300
35
11; 6,3
Yn/D-11
8,0
46,5
7,5
0,3

Overall and Mounting Dimensions

Overall Dimensions of Transformers
Transformer type
Overall dimensions, mm
Weight, kg
L B H H1 H2 H3 N K b b1 Total Transport Oil
TMNP-2500/35
3200
2300 3330 2020 280 723 400 200 280 205 9145 7700 2120
TMNP-4000/35
3400 3190 3550 2390 275 723 400 240 285 230 11498 9418 2980
TMNP-6300/35
4200 3230 3800 2660 275 723 400 240 310 260 14995 11505 3300

Dimensional drawings

print
Power transformer, three-phase, two-winding, with natural oil circulation, equipped with on-load tap changer (OLTC). Automatic control is provided by a controller supplied together with the transformer. Designed for use in electric power transmission systems, ensuring minimized transmission losses in power lines. Skid-mounted (mobile) design. TMNP-type transformers ensure reliable power supply throughout their service life.
Get the cost
Please fill in all fields with *
Application sent

By clicking the “Calculate” button, you consent to the processing of personal data.

team
Tusov Artem Aleksandrovich
Deputy Director for Marketing and Sales

Can't decide?

Consultation and equipment selection over the phone

Your name

Phone

Your application has been submitted for development
[10]
By clicking the “Request a call” button, you consent to the processing of personal data.