HV winding rated voltage: 110(154) kV
MV winding rated voltage: 38.5 kV
LV winding rated voltage: 27.5 kV
T — Three-phase transformer
F — Side-mounted bushings configuration
T — Three-winding transformer
P — Designed for traction power supply of electrified railways and converter units
X — Rated power, kVA
110(150) — Voltage class, kV
U1 / UHL1 — Climatic version and installation category in accordance with GOST 15150
| Main Technical Characteristics | ||
| Parameter name | TFTP-31500/110 | TFTP-31500/150 |
| No-load losses, kW | 33 | 33 |
| Short-circuit losses, kW | 169 | 169 |
| No-load current, % | 0.6 | 0.6 |
| Short-circuit voltage (HV–MV), % | 10.5 | 10.5 |
| Short-circuit voltage (HV–LV), % | 17.5 | 17.5 |
| Short-circuit voltage (MV–LV), % | 6.5 | 6.5 |
| Overall dimensions, mm | ||
| L — length | 7500 | 7600 |
| B — width | 3250 | 3250 |
| H — height | 3850 | 3850 |
| Oil weight, kg | 17300 | 17300 |
| Shipping weight, kg | 62700 | 62700 |
| Total weight, kg | 73000 | 73000 |