Rated power range: 10,000÷16,000 kVA.
HV winding rated voltage:
36.75; 35 kV.
Climatic category: U1 or UHL1.
T – Transformer
D –
Natural oil circulation and forced air cooling
N –
On-load tap changer (OLTC)
S – Designed for auxiliary power systems of power plants
H – Rated power, kVA.
35 – Voltage class, kV.
U1 or UHL1 –
Climatic category and installation type in accordance with GOST 15150
| Technical characteristics for TDNS-10000÷16000/35-U1(UHL1) type tranformers, energy-efficient,with reduced losses | ||||||||
|
Transformer type |
Rated power, kVA |
Rated voltage, kV | Winding connection diagram and vector group |
Losses, kW |
Short-circuit voltage, % |
No-load current, % |
||
| HV | LV |
No-load |
Short-circuit | |||||
|
TDNS-10000/35 |
10000 | 36,75 | 10,5; 6,3 | Yn/D-11 |
11,5 |
60,0 |
8,0 |
0,75 |
|
TDNS-16000/35 |
16000 | 36,75 | 10,5; 6,3 | Yn/D-11 |
17,0 |
85,0 |
10 |
0,70 |
|
Overall dimensions of TDNS-10000–16,000/35-U1 (UHL1) type transformers
|
||||||||||||
|
Transformer type |
Overall dimensions, mm | Weight, kg | ||||||||||
|
L
|
B
|
H
|
H1
|
H2
|
H3
|
A | N | K | Total | Transport | Oil | |
| TDNS-10000/35
|
4125
|
3265
|
3685
|
1935
|
550
|
995
|
1524
|
1000
|
300 | 19430 | 16260 | 4100 |
| TDNS-16000/35
|
4470
|
3415
|
3922
|
135
|
585
|
850
|
1524
|
1000
|
400 | 26000 | 22145 | 5250 |