Rated power: 25,000 kVA
HV winding rated voltage: 36.75 kV
Climatic category: U1 / UHL1
Т – Three-phase transformer
R – Split
LV
winding
D – Natural oil circulation and forced air cooling
N – On-load tap changer (OLTC)
S – Designed for auxiliary power systems of power plants
Х – Rated power, kVA
35 – Voltage class, kV
U1 or UHL1 –
Climatic category and installation type in accordance with GOST 15150
|
Technical characteristics for TRDNS-25000/35-U1 (UHL1) type transformers, energy-efficient design with reduced losses
|
||||||
|
Transformer type
|
Rated power, kVA
|
Rated voltage, kV
|
Winding connection diagramand vector group
|
Losses, kW
|
||
| HV | LV |
No-load
|
Short-circuit
|
|||
| TRDNS-25000/35
|
25000
|
36,75 35
|
6,3-6,3 6,3-10,5; 10,5-10,5
|
Yn/D-11-11
|
16
|
105
|
|
Overall dimensions of TRDNS-25000/35-U1 (UHL1) type transformer
|
|||||||
|
Transformer type
|
Short-circuit voltage, %
|
No-load current, %
|
Weight, kg
|
||||
|
ВН-НН1+НН2
|
ВН-НН1 или ВН-НН2
|
НН1-НН2
|
Total weight
|
Transport weight
|
Oil weight
|
||
| TRDNS-25000/35
|
10,5
|
23
|
не менее 40
|
0,3
|
42795
|
37650
|
9660
|