Quality in every coil. Reliability in every delivery.
ico
ico ico En ico
Color scheme:
A A A
Font size:
A A A A A
Copyright © 2026 AO "Чирчикский Трансформаторный Завод"
ico
Color scheme:
A A A
Font size:
A A A A A
sound Screen reader
The website features screen reader. To listen to the text, simply highlight it with the mouse and click on the appearing icon.

TDTN-25000–63000/220-U1 (UHL1) type three-winding power transformers with on-load tap changer (OLTC)

product
Power transformer, three-phase, three-winding, with natural oil circulation and forced air cooling, equipped with on-load tap changer (OLTC) and DETC (off-circuit tap changer). Automatic control is provided by a controller supplied together with the transformer. TDTN-type transformers ensure reliable power supply throughout their service life.
Get the cost
Application sent

By clicking the “Calculate” button, you consent to the processing of personal data.

Description

Power transformer, three-phase, three-winding, with natural oil circulation and forced air cooling, equipped with on-load tap changer (OLTC) and DETC (off-circuit tap changer). Automatic control is provided by a controller supplied together with the transformer. TDTN-type transformers ensure reliable power supply throughout their service life.

Power range

Rated power range: 25000–63000 kVA
HV winding rated voltage : 158 kV
MV winding rated voltage : 38.5 kV
Climatic category: U 1 or UHL 1

Transformer symbols

T Three-phase transformer
  Natural oil circulation and forced air cooling
T Three-winding
On-load tap changer (OLTC)
Х Rated power, kVA
150 HV voltage class, kV
U1 / UHL1 Climatic category and installation type in accordance with GOST 15150

Characteristic

Technical characteristics for TDTN-25000–63000/220-U1 (UHL1) type transformers
Parameter
Value
Transformer type
TDTN
Rated power, kVA
25000
40000
63000
Rated voltage, HV winding, kV
-
Rated voltage, MV winding, kV
38,5
Rated voltage, LV winding, kV
6,6; (11,0)
Winding connection diagram and vector group
Yn/Yn/D-0-11
No-load losses, kW
45 54 65
Short-circuit losses, kW
130 220 285
Short-circuit voltage, HV-MV, % 12,5 12,5 11,0
Short-circuit voltage, HV-LV, % 20 22,0 18,5
Short-circuit voltage, MV-LV, % 6,5 9,5 6,5
No-load current, % 0,7 0,5 0,7
Dimensions, mm
L (length) 9600 9000 8400
B (width) 5150 5350 4750
H (height) 8050 7350 7200
Oil weight, kg 31000 35000 37400
Shipping weight, kg 90000 100000 105500
Total weight, kg 110000 115000 118500

Dimensional drawings

print
Power transformer, three-phase, three-winding, with natural oil circulation and forced air cooling, equipped with on-load tap changer (OLTC) and DETC (off-circuit tap changer). Automatic control is provided by a controller supplied together with the transformer. TDTN-type transformers ensure reliable power supply throughout their service life.
Get the cost
Please fill in all fields with *
Application sent

By clicking the “Calculate” button, you consent to the processing of personal data.

Other offers

Explore other options of our equipment