Rated power range: 25–1600 kVA
T — Three-phase transformer
M — Oil-immersed transformer with natural air and oil circulation
Zh — Railway application transformer
X — Rated power, kVA
27.5 — HV winding rated voltage, kV
U1 — Climatic category and installation type in accordance with GOST 15150
|
Technical Characteristics
for TMZh transformers, rated 25
÷
1600 kVA
|
||||||
|
Rated power, kVA
|
Rated voltage, kV
|
Winding connection diagram and vector group
|
Losses, W
|
Short-circuit voltage, %
|
No-load current, %
|
|
|
No-load
|
Short-circuit
|
|||||
| 25
|
27,5/0,4
|
У/Ун-0
|
175
|
610
|
6 | 2,0
|
| 100
|
27,5/0,4
|
У/Ун-0; Д/Ун-11
|
380
|
1970
|
6 | 1,2
|
| 160
|
27,5/0,4
|
У/Ун-0; Д/Ун-11
|
560
|
2650
|
6 | 1,0
|
| 250
|
27,5/0,4
|
У/Ун-0; Д/Ун-11
|
800
|
3700
|
6 | 0,8
|
| 400
|
27,5/0,4
|
У/Ун-0; Д/Ун-11
|
1090 |
5900
|
6 |
0,6
|
| 630
|
27,5/0,4
|
Д/Ун-11
|
1700
|
8500
|
6 | 0,5
|
| 1000
|
27,5/0,4
|
У/Ун-0
|
2000
|
1150
|
7,2 | 0,4
|
| 1600 | 27,5/0,4 | У/Ун-0 | 2750 | 18000 | 7,2 | 0,3 |
|
Transformer overall dimensions
|
|||||||
|
Rated power, kVA
|
Length (L), mm
|
Width (B), mm
|
Height (H), mm
|
Distance between channel centerlines
|
Oil weight, kg
|
Total weight, kg
|
|
|
Longitudinal axis (A), mm
|
Transverse axis (A1), mm
|
||||||
|
25
|
1040
|
820
|
1310
|
400
|
550
|
175
|
600
|
|
100
|
1200
|
840
|
1640
|
420
|
605
|
310
|
1040
|
|
160
|
1300
|
860
|
1700
|
420
|
605
|
380
|
1290
|
|
250
|
1400
|
930
|
1890
|
420
|
605
|
330
|
1700
|
|
400
|
1460
|
960
|
2000
|
760
|
760
|
565
|
2095
|
|
630
|
1950
|
1240
|
2130 |
820
|
820
|
950
|
3500
|
|
1000
|
2310
|
1270
|
2385
|
1070
|
1070
|
950
|
3850
|
| 1600 | 2610 | 1285 | 2560 | 1070 | 1070 | 1340 | 4800 |